Permit Information
Permit NumberFIR15-00767
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 619 W BANNOCK ST
Project NameAT&T Fire Alarm Replacement
Customer Number 
ePlanReviewYes
Description
AT&T FA Replacement work is the replacement of building fire alarm/detection system (less air sampling systems - to remain) with new addressable system. New system will also monitor all fire protection devices including pumps, flow switches, valves equipped with tamper switch, etc.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/20/20169/21/20169/21/2016APASS
DetailsJim Page
Final fire alarm inspection passed/complete.
INSP-Final Inspection9/15/20169/20/20169/20/2016ACANC
DetailsJim Page
Inspection request was moved to this afternoon, due to scheduling issues for this afternoon this inspection request is cancelled and will be rescheduled for 10am on 21SEPT2016.
INSP-Alarm Testing6/22/20166/23/20166/23/2016ADONE
DetailsJim Page
Alarm testing complete, all devices with the new fire alarm system has been tested. A 10% functionality test will be performed on the new fire alarm system after the old fire alarm system and components have been removed. Note that the 5th floor pre-action isolation valve has a visible leak on the valve (leaks in the fire sprinkler system has the potential to cause false alarms), leak needs to be repaired before fire alarm system will by signed off as complete,
INSP-Final Inspection6/14/20166/15/20166/15/2016APART
DetailsJim Page
Tested smokes and A/V's on level 7, level 6, level 5 and level 4, all devices tested properly. Tested elevator recall as well as elevator shunt trip, devices tested corectly. Tested HVAC unit shutdown for in-duct smoke detectors on level 2, all tested correctly. Items left to inspect, associated devices with fire sprinkler system and VESDA systems.
INSP-Final Inspection5/10/20165/11/20165/11/2016APART
DetailsJim Page
Project is being worked in phases, contractor is going floor by floor for partial inspection and a final alarm inspection for entire building at project completion. Inspected level 3 smoke detectors and pull stations, remaining detection on level 3 is VESDA systems which will be tested at a later date. Level 1 smoke detectors/duct detectors/pull stations spot checked, devices tested operated correctly. Level 1 inspection complete, partial completion for level 3, contractor will schedule inspection request when other area's are ready.
INSP-Final Inspection3/8/20163/9/20163/9/2016APART
DetailsJim Page
Project is being worked in phases, contractor is going floor by floor for partial inspection and a final alarm inspection for entire building at project completion. Inspected basement level alarm system install with device testing, basement level inspection is passed/complete, contractor will schedule remaining floors for later date.
INSP-Conference1/5/20161/6/20161/6/2016ADONE
DetailsJim Page
Fire alarm conference complete.