Permit Information
Permit NumberFIR15-00794
StatusFinaled
Name PROTEX
Site Address 1111 W JEFFERSON ST Unit: 500
Project NamePerkins Coie
Customer Number 
ePlanReviewYes
Description
Modification of an existing fire alarm system to accommodate a tenant remodel on the 5th floor. Associated with building permit BLD15-02346.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/21/20164/21/20164/21/2016PPASS
DetailsJim Page
Final fire alarm inspection passed/complete
INSP-Final Inspection3/21/20163/21/20163/21/2016PPART
DetailsJim Page
Final alarm testing complete for phase 2, contractor will schedule final inspection for phase 3 when complete.
INSP-Final Inspection3/16/20163/17/20163/17/2016ACANC
DetailsJim Page
Inspection request cancelled per conversation with point of contatct, Morgan Phone #: ###-####, contractor will reschedule inspection for later date.
INSP-Final Inspection1/7/20161/8/20161/8/2016APART
DetailsTroy Cobbley
Todays inspection was just to verify that the visual devices sync'd in phase one which they did.
INSP-Final Inspection12/30/201512/30/201512/30/2015PFAIL
DetailsJim Page
Verified spacing and placement of Audio/Visual devices. Area of inspection passed for device placement, strobes need to be syncronized together when strobes are in same area. Contractor will reschedule inspection when sync issue repaired.