INSP-Final Inspection | 8/18/2016 | 8/18/2016 | 8/18/2016 | P | PASS |
Jim Page
|
|
|
Previously noted items have been repaired, ceiling fans that were located to close to smoke detectors have been removed and covers installed over electrical boxes at time of inspection. Flow switch, backlow tamper switches and post indicator valve on fire sprinkler system all tested correctly. Batteries were changed to 7 amp hour batteries to coincide with city approved drawings. Final fire alarm inspection passed/complete.
|
INSP-Final Inspection | 8/8/2016 | 8/8/2016 | 8/8/2016 | P | FAIL |
Troy Cobbley
|
|
|
We did not perform any actual testing today. I noted that the forward flush vavle was wired wrong, missing ceiling mounted horn/strobe, wrong batteries in the facp and four Bedrooms with the smoke detectors mounted less than 3'-0" from ceiling fans, PIV took 4 turns to activate tamper switch and the flow switch timing has not been verified.
|