INSP-Final Inspection | 6/1/2016 | 6/2/2016 | 6/2/2016 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/26/2016 | 5/26/2016 | 5/26/2016 | A | FAIL |
Troy Cobbley
|
|
|
Duct smoke detectors have been tested. To final this permit plan modifications will be required for the additional NAC panel and associated horn/strobes and then of course the testing of these devices.
|
INSP-Final Inspection | 5/24/2016 | 5/25/2016 | 5/25/2016 | P | FAIL |
Troy Cobbley
|
|
|
Head end equipment was verified. Interconnects with the fire sprinkler system were verified. I then did a walk through on the notification devices and noted several at the wrong candella and in one location nine new strobes will need to be added. Several locations have 15cd strobes mounted outside of their listing at 12"-0"
|
INSP-Final Inspection | 5/23/2016 | 5/24/2016 | 5/24/2016 | P | CANC |
Troy Cobbley
|
|
|
Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price
|