Permit NumberFIR16-00045
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 515 W IDAHO ST
Project NamePaulsen Building
Customer Number 
ePlanReviewYes
Description
This is a retrofit of an existing two level building with a basement. The building will have full NFPA 13 sprinkler coverage.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/16/20168/17/20168/17/2016PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/16/20168/17/20168/17/2016APASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection8/11/20168/16/20168/16/2016PFAIL
DetailsTroy Cobbley
Need sticker on the outside alarm bell and test papers.
INSP-Final Inspection8/11/20168/12/20168/11/2016PCANC
DetailsJim Page
Please call 30 minutes prior to arriving as we are not on site Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in/Hydro2/23/20162/23/20162/23/2016PPASS
DetailsJim Page
Overhead hydrostatic test passed/complete for entire project. Rough to cover inspection complete for hard-lids, hard-lids approved for cover.
INSP-Supply line flush2/17/20162/18/20162/18/2016ADONE
DetailsJim Page
Underground main line flush complete.
INSP-Sprinkler Rough-in/Hydro2/17/20162/17/20162/17/2016PPASS
DetailsJim Page
Underground hydrostatic test (200psi for 2 hours) passed/complete. Remote FDC hydrostatic test (200psi for 2 hours) passed/complete
INSP-Sprinkler Rough-in2/10/20162/11/20162/11/2016APASS
DetailsJim Page
Underground remote FDC inspection passed/complete, approved for cover.
INSP-Sprinkler Rough-in2/10/20162/10/20162/10/2016PPASS
DetailsJim Page
Rough to cover inspection passed/complete for the underground fire sprinkler supply line, underground approved for cover.