Permit Information
Permit NumberFIR16-00070
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 1401 S ROBERT ST
Project NameWells Fargo Fin. Flr 2 FA
Customer Number 
ePlanReviewYes
Description
Replace the outdated fire alarm smoke detectors, pull stations, and duct detector on the second floor and first floor main entry. Also add full horn/strobe notification in remodeled areas in order to bring those areas up to code. Work will take place during the second floor remodel and first floor main entry remodel.
Building currently has full smoke detection and pull stations at each exit. Associated with byulding permit BLD15-04361.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/21/20166/22/20166/22/2016APASS
DetailsJim Page
Previously noted items have been addressed/repaired. Final fire alarm inspection passed/complete
INSP-Final Inspection6/14/20166/16/20166/16/2016AFAIL
DetailsTroy Cobbley
Resubmit plans showing the three peaked sky lights with additional protection and show the two ceiling levels that surround the sky lights, show candella changes on the second floor, provide sync for all notification devices, provide additional notification in the basement lobby, provide the sample tubes and remote annunciators for the duct smoke detectors. The only devices tested today was the first floor lobby manual pull station, four fire/smoke damperson the first floor and the south duct detector on the second floor. All other devices need to be tested. I noted that the first floor manual pull station activated elevator recall which is not allowed in current code.
INSP-Final Inspection6/14/20166/15/20166/14/2016ACANC
DetailsJim Page
If you cannot reach me, please call Kenny Leslie @ ###-####
or Mike Kroll @ ###-#### Phone #: ###-#### >> Inspection requested via web by Josiah Monett Inspection cancelled from web by: Josiah Monett