INSP-Final Inspection | 7/8/2016 | 7/11/2016 | 7/11/2016 | A | PASS |
Jim Page
|
|
|
Previously noted items addressed/repaired, final fire sprinkler inspection passed/complete.
|
INSP-Final Inspection | 7/5/2016 | 7/5/2016 | 7/5/2016 | P | FAIL |
Troy Cobbley
|
|
|
Provide inspectors test/drain as per approved plans, riser in garage closet needs to be installed with-in 1 1/2" of wall or needs to be steel, most of the piping in the basement does not meet the installation requirements for exposed piping in unfinished basements per the Spears Manual.
|
INSP-Sprinkler Rough-in | 2/29/2016 | 2/29/2016 | 2/29/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection completed, including tenting for fire sprinkler piping located in attic space, complete area of work approved for cover.
|