Permit NumberFIR16-00100
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 465 W GOWEN RD
Project NameBoise School Dist. Storage Bld
Customer Number 
ePlanReviewYes
Description
Install a new Dry Pipe sprinkler system throughout the new structure. Install new Dry Valve complete with air compressor and FDC located on the wall of the riser room.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/14/201612/15/201612/15/2016APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Sprinkler Rough-in/Hydro9/27/20169/29/20169/29/2016PPASS
DetailsJim Page
24 hour air test for dry system complete.
INSP-Sprinkler Rough-in/Hydro9/27/20169/28/20169/28/2016APART
DetailsJim Page
200 psi hydrostatic test for overhead fire sprinkler piping complete. Rough in inspection for overhead fire sprinkler piping complete. 24 hour air test started at 11:00AM 28SEPT2016 with 40psi on gauge.