Information based on query as of Thursday, June 27, 2024.
Permit Information
Permit NumberFIR16-00132
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 7640 W STATE ST
Project NameNorth Point Retail Building 1
Customer Number 
ePlanReviewYes
Description
Provide sprinkler monitoring for a new shell and core building. Associated with building permit BLD15-03583.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/30/20167/1/20167/1/2016APASS
DetailsJim Page
Final fire alarm inspection passed/complete
INSP-Final Inspection6/13/20166/14/20166/14/2016PPART
DetailsJim Page
Fire alarm inspection partially complete, tested/inspected waterflow, tampers, smoke detector above fire panel and pull station, HVAC units are over 2000cfm so HVAC untis require duct detectors with unit shutdown (induct detectors are shown on city approved drawings), HVAC units do not have power connected so duct detectors were INOP at time of inspection. Duct detectors need to be in operation or general contractor needs to have documentation from the city supporting the duct detectors being INOP.