Permit Information
Permit NumberFIR16-00135
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7640 W STATE ST
Project NameNorth Pointe #1 - Underground
Customer NumberUDG ONLY
ePlanReviewYes
Description
[North Pointe Retail Building #1- Udg Only] - Quick Permit
Install a new 4"x 73' +- C-900 underground piping, fittings and thrust blocks. UDG only on this submittal.

(NORTH POINTE RETAIL – BLDG #1 – Shell and Core) Permit is to construct a 4,966 square foot Retail / Office / Assembly Shell building. This building is constructed as a wood frame building and a concrete footing. Work includes: new foundation, new exterior walls, new mechanical, stubbing in plumbing into the building, site work, new wood frame exterior walls, new manufactured wood truss roof system, and new electrical (Exterior Lighting Approved). This building will be fully Fire Sprinklered with an approved Fire Alarm system. System shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. NOTE: In accordance with Section C401.2 option #1 of the 2012 IECC; ANSI/ASHREA/IESNA 90.1 were used to show compliance with the Energy Code. The lighting installed within the tenant spaces shall also comply with ASHREA. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/13/20166/14/20166/14/2016PPASS
DetailsJim Page
Final underground supply inspection passed/complete
INSP-Final Inspection6/13/20166/14/20166/13/2016ACANC
DetailsJim Page
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Supply line flush4/5/20164/6/20164/6/2016ADONE
DetailsJim Page
Underground main line flush complete
INSP-Supply line flush3/18/20163/18/20163/18/2016APASS
DetailsJim Page
Rough to cover inspection complete for the underground supply, underground approved for cover. Underground hydrostatic test (200 psi for 2 hours) passed/complete