Description
Sprinkler monitoring and duct detection. Associated with building permit BLD15-03584.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/26/20167/27/20167/27/2016APASS
DetailsJim Page
Final fire alarm inspection passed/complete
INSP-Final Inspection6/13/20166/14/20166/14/2016PPART
DetailsJim Page
Fire alarm inspection partially complete, tested/inspected waterflow, tampers, smoke detector above fire panel and pull station, HVAC units are over 2000cfm so HVAC untis require duct detectors with unit shutdown, HVAC units do not have power connected so duct detectors were INOP at time of inspection. Duct detectors need to be in operation or general contractor needs to have documentation from the city supporting the duct detectors being INOP.