Permit Information
Permit NumberFIR16-00145
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2772 S COLE RD Unit: 110
Project NameFELLERS TI
Customer Number 
ePlanReviewYes
Description
[Fellers TI]
The fire sprinkler scope of work consists of revamping an existing grid system to allow for storage of group A plastics up to 15’. A new 8” feed main and 6” cross-main are being added. The existing riser is being changed to 8” with an 8” backflow preventer. The existing sprinkles are being removed and plugged. New K=16.8 are being added.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/28/20164/29/20164/29/2016APASS
DetailsTroy Cobbley
Permit finaled
INSP-Supply line flush4/7/20164/8/20164/8/2016APASS
DetailsTroy Cobbley
Forward flow test of the backflow preventor passed
INSP-Sprinkler Rough-in/Hydro4/7/20164/7/20164/7/2016PPASS
DetailsTroy Cobbley
The new piping has been tied into the existing system. Hydro static test a city pressure passed. Tim is ok with the 8" lateral siesmic bracing connecting to the bottom chord of the girder. Need alarm interconnects and forward flush for final.
INSP-Sprinkler Rough-in/Hydro4/4/20164/5/20164/5/2016APASS
DetailsTroy Cobbley
Overhead r/i and hydro test for the 8" and 6" mains passed.
INSP-Sprinkler Rough-in/Hydro4/4/20164/4/20164/4/2016PPART
DetailsTroy Cobbley
Overhead for just the main piping passed except I need verification that the lateral siesmis bracing can be attatched to the bottom chord of the truss/girder. Riser nipples not instlled or attached yet. The overhead hydro failed due to a visible loss of pressure at the guage.