Information based on query as of Wednesday, June 26, 2024.
Permit Information
Permit NumberFIR16-00185
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 715 S CAPITOL BLVD
Project NameBoise Main Library - HVAC upgr
Customer Number 
ePlanReviewYes
Description
2nd Floor HVAC upgrade at main Boise Public Library. Fire alarm systemd changes are to include new smoke detectors, smoke duct detectors and notification. Associated with building permit BLD15-04544.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/18/20168/18/20168/18/2016PPASS
DetailsJim Page
Previously noted items have been repaired, final fire alarm inspection passed/complete.
INSP-Final Inspection6/21/20166/22/20166/22/2016AFAIL
DetailsKatie Marron
The smoke detectors and strobes on 2nd floor verified "OK". Duct detectors did not shut down fan. Following items needed:
- Updated map of devices at panel
- Junction box cover by relays in mech room
- Retest of duct detectors to verify fan shut down