Permit Number | FIR16-00198 |
Status | Finaled |
Name |
CURTIS FIRE SPRINKLER SERVICE INC
|
Site Address |
567 W PASO FINO DR
|
Project Name | Soltau Res. addition |
Customer Number | |
ePlanReview | Yes |
Description |
[Soltau Residence Addtion] - Quick Permit
Addition to living room of an existing 13D sprinkled home. Orig design calc done on 2nd floor @ 18'x18'(17gpm min) - this install 1st floor close to riser based on 16'x16'(13gpm min).
(Plan mode on 3-7-16, resubmitted engineering. See documents. **BJM**) Enclosing exisiting back patio to become Living Space. Existing doors from Living Room to be removed, floor to be built up to match exisitng, R10 rigid insulation to be placed between 2x treated sleepers. Prescriptive Energy Code to be used. Fire Sprinklers are required, plans and design to be submitted and approved per Tim Cross. See engineering notes that shall be provided. **DAF**
|