[Kensington Apartments - Building O Standpipes]
The fire sprinkler scope of work consists of a NFPA 14 standpipe system ONLY. The fire sprinklers are a deferred submittal. There will be two manual dry standpipes. The standpipes are to be interconnected per NFPA 14. The FDC is to have locking Knox caps per alternate agreement with the fire marshal.
Note: To achieve 500 Gpm @ 100 Psi a the top most standpipe outlets the fire apparatus is required to supply 767.5 Gpm @ 145.1 Psi
The underground for buildings T, O & P are under permit FIR15-00689
(THE KENSINGTON APARTMENTS - BUILDING O) The drawings are filed under BLD15-01107 in ePlanReview. The NFPA 13-R fire sprinkler system is used for occupancy and for story increase. To construct a 19,568 square foot four story apartment building (5,243 sq. ft. 1st story with four 2.c units, 5,192 sq. ft. 2nd story with four 2.c units, 5,192 sq. ft. 3rd story with four 2.c units, and 3,941 sq. ft. 4th story with four 1.d units). All ground floor units are required to comply as Type B dwelling units. No elevator is provided in this building. Work is to include concrete footings, concrete foundations, concrete slabs on grade, wood stud bearing walls, wood stud shear walls, fiberglass shingles, fiber-cement board siding, manufactured stone veneer, 1-hr dwelling unit separations, .5-hr minimum fire-resistance-rated corridors with 20 minute smoke- and draft-control doors, exterior exit stairways fire rated like the corridor, steel stairways with concrete treads, interior nonbearing walls, millwork, and finishes. Special Inspection is required for soils and for concrete. The roof truss design is a deferred submittal item. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13-R and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
|