INSP-Final Inspection | 9/14/2016 | 9/15/2016 | 9/15/2016 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection passed/complete.
|
INSP-Sprinkler Rough-in/Hydro | 8/3/2016 | 8/3/2016 | 8/3/2016 | A | PASS |
Jim Page
|
|
|
24 hour air test for new dry system install passed/complete.
|
INSP-Sprinkler Rough-in/Hydro | 8/1/2016 | 8/2/2016 | 8/2/2016 | A | PART |
Jim Page
|
|
|
200 psi hydrostatic test complete, 24 hour air test started at 12:00 pm @ 40psi
|
INSP-Sprinkler Rough-in | 8/1/2016 | 8/1/2016 | 8/1/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping located above ceiling grid area's complete, approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 5/6/2016 | 5/6/2016 | 5/6/2016 | P | PASS |
Jim Page
|
|
|
Hydrostatic test complete for overhead wet system in northeast 50 degree cooler, hydrostatic test complete for dry system located northwest 38 degree cooler.
|