Permit Number | FIR16-00244 |
Status | Finaled |
Name |
VIKING AUTOMATIC SPRINKLER CO
|
Site Address |
481 W GOWEN RD
|
Project Name | Boise School Dist. Main Bldg |
Customer Number | |
ePlanReview | Yes |
Description |
[Boise School District Operations and Maintenance Building]
The fire sprinkler scope of work consists of protecting a new building with a wet and dry system utilizing new 8”x30’± C-900 underground piping. A new NFPA 20, 1500 Gpm @ 62 Psi fire pump will be installed in a dedicated fire pump room. The metal building is primarily one level, which is divided into individual sections and occupancies (Somewhat similar to a strip mall in its design.) There is an extensive mezzanine system and an 11000 ft^2 office area. The sprinkler system is designed primarily as OH 2, however, there is a warehouse area utilizing ESFR sprinklers based on Group A plastics. There are several thousand gallons of various hazardous materials all below MAQ. There are also two outside double wall underground storage tanks (gasoline, diesel)
(BOISE SCHOOL DISTRICT OPERATIONS & MAINTENANCE BUILDING – Building “A”) Permit to include construction of a 50,564 square foot building primarily used as office area and a vehicle repair shop. PLAN MODIFICATION 2-23-15 – Modification submitted to value engineer the mechanical system and related work. **TLW** This building is fire sprinklered for area increases. Work to include: concrete foundation, typical metal building structural frame, interior partitions to create several offices, several separate warehouses, 7 separate mezzanines each under 3,000 square feet and each for separate “tenants” within the overall building, new plumbing, new mechanical, new electrical, and interior finishes in compliance with chapter 8 of the 2012 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**
|