Information based on query as of Thursday, June 20, 2024.
Permit Information
Permit NumberFIR16-00251
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 3077 N CHRISTINE ST
Project NameIslamic Center of Boise
Customer Number 
ePlanReviewYes
Description
Fire Sprinkler monitor system with full notification due to occupant load. Associated with building permit BLD15-02839. Central station monitoring is being provided by Crane Alarm.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/9/20172/10/20172/10/2017PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection2/9/20172/10/20172/9/2017PCANC
DetailsTroy Cobbley
Late afternoon - Casey Phone #: ###-#### Inspection cancelled from web by: John Siewert
INSP-Final Inspection12/22/201612/27/201612/27/2016AFAIL
DetailsTroy Cobbley
Need the knox box, need weather proof devices in the shower areas and Crane Alarm needs to be present to test the AES system that they have an open permit for.
INSP-Final Inspection12/9/201612/9/201612/9/2016PFAIL
DetailsJim Page
No document cabinet by fire panel, wall between storage rooms 2 and 3 has been removed, verified removal on city approved structural drawings, room is designated as "Social Room", social room needs an audio/visual device added per code requirement, device addition will require a resubmittal. Audio/visual devices did not latch into alarm during waterflow, when flow was stopped audio/visuals silenced without command. A knox box will be required due to the building having a monitored fire alarm system. Mens restroom has what appears to be a shower that is not complete, audio visual device needs to be changed to a weather proof type device.