INSP-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 10/31/2017 | 10/31/2017 | 10/31/2017 | P | FAIL |
Troy Cobbley
|
|
|
Provide minor corrections as discussed with the pipe clearance and pipe straps. Need test papers
|
INSP-Final Inspection | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | FAIL |
Troy Cobbley
|
|
|
Not ready for final yet but we did test the dry pipe system and the interconnection with the fire alarm panel. It appears that a rough-in inspection is still needed for the garage.
|
INSP-Final Inspection | 10/24/2017 | 10/25/2017 | 10/25/2017 | P | FAIL |
Troy Cobbley
|
|
|
Not all items tested today due to time constraints. See the on site fire alarm as-built plans for the sprinkler devices tested today as marked "ok".
|
INSP-Final Inspection | 10/24/2017 | 10/24/2017 | 10/24/2017 | P | CANC |
Troy Cobbley
|
|
|
Before 2:00 am or after 3:00 call ahead the elevator guy can’t be here between 2:00 and 3:00. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
INSP-Sprinkler Rough-in/Hydro | 10/19/2017 | 10/20/2017 | 10/20/2017 | A | PASS |
Jim Page
|
|
|
24 hour air test complete.
|
INSP-Sprinkler Rough-in/Hydro | 10/18/2017 | 10/19/2017 | 10/19/2017 | A | DONE |
Troy Cobbley
|
|
|
24 hour air test on dry system started at 8:45 with 44psi on the guage.
|
INSP-Sprinkler Rough-in/Hydro | 10/18/2017 | 10/18/2017 | 10/18/2017 | P | PASS |
Troy Cobbley
|
|
|
200 psi Hydro test on dry system passed
|
INSP-Sprinkler Rough-in/Hydro | 10/17/2017 | 10/17/2017 | 10/17/2017 | P | FAIL |
Troy Cobbley
|
|
|
Hydro test of the dry system failed due to visible loss of pressure at the guage.
|
INSP-Sprinkler Rough-in/Hydro | 10/12/2017 | 10/13/2017 | 10/13/2017 | A | PASS |
Troy Cobbley
|
|
|
Hydro on first/second/ third floor passed
|
INSP-Sprinkler Rough-in | 9/20/2017 | 9/21/2017 | 9/21/2017 | A | PASS |
Troy Cobbley
|
|
|
First and second floor corridor grid ceiling are ok for cover.
|
INSP-Sprinkler Rough-in | 9/8/2017 | 9/8/2017 | 9/8/2017 | P | PASS |
Troy Cobbley
|
|
|
Trash shoots 2nd floor 3rd floor and trash shoot room sprinkler work is complete. Also the sprinkler piping for the 3rd floor Corridor is ok to cover. Suite 106 sprinkler work is complete..
|
INSP-Sprinkler Rough-in | 9/1/2017 | 9/5/2017 | 9/5/2017 | A | PASS |
Troy Cobbley
|
|
|
The fire sprinkler work in Suites 203, 204, 205, 206 and 302 is passed. The Closet light in Suite 106 still needs rotated. The Pantry head in Suite 101 has been corrected. I noted that a pendant is painted in Suite 208.
|
INSP-Sprinkler Rough-in | 8/31/2017 | 9/1/2017 | 9/1/2017 | A | PART |
Troy Cobbley
|
|
|
Todays walk through was for the first floor apartments. I noted one painted concealer pendant head and on pendant that is blocked by a surface mounted light.
|
INSP-Sprinkler Rough-in | 8/2/2017 | 8/3/2017 | 8/3/2017 | A | PASS |
Troy Cobbley
|
|
|
Installed verifed 2 dry flex heads in the breezeway on Ground Level. Piping is ok to cover.
|
INSP-Sprinkler Rough-in | 7/6/2017 | 7/7/2017 | 7/7/2017 | A | PASS |
Troy Cobbley
|
|
|
First floor north corridor soffits are ok to cover and the south building Guest Room
|
INSP-Sprinkler Rough-in | 7/5/2017 | 7/5/2017 | 7/5/2017 | P | PASS |
Troy Cobbley
|
|
|
Second floor cover for the soffits is ok for cover in the corridor.
|
INSP-Sprinkler Rough-in | 6/26/2017 | 6/27/2017 | 6/27/2017 | A | PASS |
Troy Cobbley
|
|
|
Third floor corridor soffits are ok to cover
|
INSP-Sprinkler Rough-in | 5/15/2017 | 5/16/2017 | 5/16/2017 | A | CANC |
Troy Cobbley
|
|
|
Duplicate inspection
|
INSP-Sprinkler Rough-in | 5/15/2017 | 5/16/2017 | 5/16/2017 | A | PASS |
Troy Cobbley
|
|
|
1st and 3rd floor south side corridor soffit heads are ok to cover. I noted one area on both the first and third floors where sprinkler pendants are less than 8' apart which is not allowed for extended coverage heads. I need verification that the heads can be that close or heads need to be relocated.
|
INSP-Sprinkler Rough-in | 4/13/2017 | 4/14/2017 | 4/14/2017 | A | PASS |
Troy Cobbley
|
|
|
Unit 107 piping is ok for cover.
|
INSP-Sprinkler Rough-in | 4/12/2017 | 4/13/2017 | 4/13/2017 | A | PASS |
Troy Cobbley
|
|
|
Unit 101 sprinkler piping can be covered.
|
INSP-Sprinkler Rough-in | 4/5/2017 | 4/6/2017 | 4/6/2017 | A | PASS |
Troy Cobbley
|
|
|
Unit 201 piping above soffits can be covered
|
INSP-Sprinkler Rough-in/Hydro | 4/4/2017 | 4/5/2017 | 4/5/2017 | A | PASS |
Troy Cobbley
|
|
|
Hydro test on the standpipes; the parking garage passed. I also did a rough-in on the standpipes and only found one floor clamp missing.
|
INSP-Sprinkler Rough-in | 4/4/2017 | 4/5/2017 | 4/5/2017 | A | PASS |
Troy Cobbley
|
|
|
Rough to cover for units 304 and 208 passed. All piping in the apartments can be covered.
|
INSP-Sprinkler Rough-in | 3/28/2017 | 3/29/2017 | 3/29/2017 | P | PASS |
Troy Cobbley
|
|
|
Rough to cover in room 301 passed. All piping can be covered.
|
INSP-Sprinkler Rough-in | 3/22/2017 | 3/23/2017 | 3/23/2017 | A | PASS |
Troy Cobbley
|
|
|
Unit 202 soffit piping can be covered. Rough-in passed.
|
INSP-Sprinkler Rough-in | 3/14/2017 | 3/15/2017 | 3/15/2017 | A | PASS |
Troy Cobbley
|
|
|
Unit 207 soffit piping passed. Piping can be covered.
|
INSP-Sprinkler Rough-in | 3/8/2017 | 3/9/2017 | 3/9/2017 | A | PASS |
Troy Cobbley
|
|
|
Unit 303 soffit piping is ok to cover.
|
INSP-Sprinkler Rough-in | 3/3/2017 | 3/6/2017 | 3/6/2017 | A | PASS |
Troy Cobbley
|
|
|
Apartment 302 lower soffits ok to cover.
|
INSP-Sprinkler Rough-in | 2/28/2017 | 3/1/2017 | 3/1/2017 | A | PASS |
Troy Cobbley
|
|
|
Rough to cover for unit 102 passed. Piping in soffits can be covered.
|
INSP-Sprinkler Rough-in | 2/27/2017 | 2/28/2017 | 2/28/2017 | A | PASS |
Troy Cobbley
|
|
|
The rough to cover on the Dry system is passed. The missing line restraints have been added
|
INSP-Sprinkler Rough-in | 2/22/2017 | 2/23/2017 | 2/23/2017 | A | PASS |
Troy Cobbley
|
|
|
Apartment 206 soffit piping is ok to cover and dry system under canopy rough-in passed. Dry piping can be covered except for the areas where branchline restraints need to be installed.
|
INSP-Sprinkler Rough-in | 2/22/2017 | 2/23/2017 | 2/22/2017 | A | CANC |
Troy Cobbley
|
|
|
206 rough in Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball Inspection cancelled from web by: Sam Ball
|
INSP-Sprinkler Rough-in | 2/20/2017 | 2/21/2017 | 2/21/2017 | A | PASS |
Troy Cobbley
|
|
|
Unit 203 piping in the soffits is ok to cover.
|
INSP-Sprinkler Rough-in | 2/15/2017 | 2/16/2017 | 2/16/2017 | A | PASS |
Troy Cobbley
|
|
|
The pendant head has been added in Apartment 204. Piping can be covered.
|
INSP-Sprinkler Rough-in | 2/14/2017 | 2/15/2017 | 2/15/2017 | P | PART |
Troy Cobbley
|
|
|
Todays inspection was for the piping in the lower soffits which is ok to cover except one head needs to be added in the Living Area. This new pendant will be verified at the next inspection.
|
INSP-Sprinkler Rough-in | 2/9/2017 | 2/9/2017 | 2/9/2017 | P | PASS |
Troy Cobbley
|
|
|
The piping in the lower soffits of apartment 205 is ok to cover.
|
INSP-Sprinkler Rough-in | 2/7/2017 | 2/8/2017 | 2/8/2017 | P | PART |
Troy Cobbley
|
|
|
Todays inspection was for apartment 205, lower soffit piping. Most piping can be covered except in the Kitchen area. There is an issue with coverage in this area that is being worked out prior to a cover approval.
|
INSP-Sprinkler Rough-in | 2/1/2017 | 2/2/2017 | 2/2/2017 | A | PASS |
Troy Cobbley
|
|
|
The modified pendant heads raised due to revised ceiling heights in Apartments 104, 105 and 106 are passed.
|
INSP-Sprinkler Rough-in | 1/30/2017 | 1/31/2017 | 1/31/2017 | A | PASS |
Troy Cobbley
|
|
|
This was a re-inspection for Apartment 103. The two pendant heads have been fixed.
|
INSP-Sprinkler Rough-in | 1/26/2017 | 1/27/2017 | 1/27/2017 | P | PART |
Troy Cobbley
|
|
|
The sprinkler piping in apartment 103 is ok to cover except in one bedroom as marked on the plans where the pendant is less than 3' to the light fixture and in the Pantry where the pendant has not been dropped yet. Will check at the re-inspection. Apartment 105 issues have been corrected.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Sprinkler Rough-in | 1/19/2017 | 1/20/2017 | 1/20/2017 | A | PART |
Troy Cobbley
|
|
|
Inspection was for Unit 105 (see plans). It appears per the obstruction charts of NFPA13R that two heads will need to be relocated. They have been marked on the plans and will be checked at the next inspection. The piping in this apartment can be covered.
|
INSP-Sprinkler Rough-in | 1/12/2017 | 1/13/2017 | 1/13/2017 | A | PART |
Katie Marron
|
|
|
Inspected drops for drop ceiling in two units on first floor. Marked which units on plans.
|
INSP-Sprinkler Rough-in | 1/4/2017 | 1/4/2017 | 1/4/2017 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for areas marked ok fo rough to cover on 3rd floor and remainder of 2nd floor
|
INSP-Sprinkler Rough-in | 12/22/2016 | 12/23/2016 | 12/23/2016 | P | PASS |
Troy Cobbley
|
|
|
See the city approved plans for specific rooms on the second floor where the rough to cover passed. Tenting deficiencies are noted in one of the apartments and it is not ok for cover
|
INSP-Sprinkler Rough-in | 12/7/2016 | 12/8/2016 | 12/8/2016 | A | PART |
Troy Cobbley
|
|
|
The two apartments at the north end of the second floor that had tenting issues are ok to cover. Also the third floor north single apartment is now ok to cover. See the city approved plans for locations marked.
|
INSP-Sprinkler Rough-in | 11/28/2016 | 11/29/2016 | 11/29/2016 | A | PART |
Troy Cobbley
|
|
|
Two of the north side, second floor apartments are ok to cover the other two need tenting corrected. Also the north end east side stairwell piping has not been tented yet. See the city approved plans for locations marked.
|
INSP-Sprinkler Rough-in | 11/17/2016 | 11/18/2016 | 11/17/2016 | A | CANC |
Troy Cobbley
|
|
|
Rough to cover on first and second floor North side up to Breezeway Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
INSP-Sprinkler Rough-in/Hydro | 11/12/2016 | 11/14/2016 | 11/14/2016 | P | PART |
Troy Cobbley
|
|
|
Todays inspection was for the sprinkler rough-in for the first and second floors. The rough-in passed on the first floor and the piping in the resident rooms can be covered. However pendant drops have not been installed to the soffits and drop ceilings yet so they will need a re-inspection prior to a complete cover inspection being given. As far as the second floor the basic rough-in passed but piping can not be covered due to tenting not being completed. Again a second inspection will be needed when the soffits and drop ceilings have been installed. I noted that in atleast one location additional fitting had to be added which requires the plans, per a note on the drawings, to be resubmitted for hydraulic calculation verification. Also the second floor plans indicate the balconies are open to above but they actually have partial roofs over them. I spoke to sam and he will follow up with plan review on a plan of action.
|
INSP-Sprinkler Rough-in/Hydro | 11/10/2016 | 11/14/2016 | 11/12/2016 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|