Permit Information
Permit NumberFIR16-00285
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 400 S CAPITOL BLVD
Project NameResidence Inn - Parking Dry
Customer Number 
ePlanReviewYes
Description
[Residence Inn - Parking Dry]
The fire sprinkler scope of work consists of partial first floor and all of the second floor as a parking area. Each floor is a separate dry system. The systems are designed as NFPA 13, OH I. There is a 750 Gpm @ 120 Psi fire pump.

The underground piping is under permit FIR16-00040
The fire pump is under permit FIR16-00090
The standpipes are under permit FIR16-00231

(RESIDENCE INN BY MARRIOTT) Permit to construct a new 204,396 square foot hotel / restaurant / assembly high-rise building. PLAN MODIFICATION 4-7-16 - Modification submitted to change cast iron plumbing to ABS plumbing. **TLW** This building consists of 8 stories of residential hotel above two stories of parking garage / restaurant. A foundation permit was issued for this project under BLD15-02707. Work to include: construction of new rated concrete building, new plumbing, new electrical, new mechanical, new fire sprinklers, new shafts, new interior partitions, and interior finishes in compliance with chapter 8 of the 2012 IBC. This building is to be fully fire sprinklered with an NFPA 13 system and fully alarmed with a NFPA 72 system. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/16/20181/17/20181/17/2018PPASS
DetailsJim Page
Final fire sprinkle rinspection for area of work complete.
INSP-Final Inspection10/9/201710/9/201710/9/2017APART
DetailsJim Page
Final fire sprinkler inspection complete, permit will remain in issued status until completion of the project.
INSP-Sprinkler Rough-in/Hydro9/28/20179/29/20179/29/2017PPASS
DetailsJim Page
24 hour air test for both dry systems complete. Trip test for both dry systems complete.
INSP-Sprinkler Rough-in/Hydro9/27/20179/28/20179/28/2017PPART
DetailsJim Page
Hydrostatic test for level 1 dry system complete. 24 hour air test start at 3:00PM @ 41PSI
INSP-Sprinkler Rough-in/Hydro9/27/20179/28/20179/28/2017APART
DetailsJim Page
24 hour air test for level 2 dry system started at 7:15AM @ 40PSI
INSP-Sprinkler Rough-in/Hydro9/26/20179/27/20179/27/2017PPART
DetailsJim Page
Hydrostatic test for level 2 dry system complete.
INSP-Sprinkler Rough-in/Hydro9/22/20179/25/20179/25/2017PCANC
DetailsJim Page
Hydrostatic test for dry system will be rescheduled for a later date, test could not be completed before the end of business day.
INSP-Sprinkler Rough-in8/1/20178/1/20178/1/2017PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping in above garage drive thru area complete (area just north of elevator lobby) approved for cover.
INSP-Sprinkler Rough-in7/14/20177/17/20177/14/2017ACANC
DetailsJim Page
Contact will be Leroy Anderson please contact him 30 min prior to Inspection start...
RTC - On 1st floor Prkg Garage drive thru area.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank