INSP-Final Inspection | 1/17/2017 | 1/18/2017 | 1/18/2017 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 1/12/2017 | 1/13/2017 | 1/13/2017 | A | FAIL |
Troy Cobbley
|
|
|
Need to change the programing of the pre-action release panel to delete the 30 countdown as discussed. All other items have been tested.
|
INSP-Final Inspection | 1/9/2017 | 1/10/2017 | 1/10/2017 | A | FAIL |
Troy Cobbley
|
|
|
Resubmit plans showing the corrected alarm activation as per discussion and address all of the items listed in the review comments. Provide "abort" outside of the room as per review note #4. provide signage and door sweep as per discussion. Raise the first and third floor nozzles to within 12" of ceiling as per notes on plans. All three wall mounted strobes are overspaced. Provide ceiling in the first floor "releasing panel room". We need to test all of the devices. Get approval to relocate the manual pull station to the inside of the room.
|
INSP-Final Inspection | 1/3/2017 | 1/6/2017 | 1/6/2017 | A | CANC |
Troy Cobbley
|
|
|
As early as possible Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, January 06, 2017.
|