Permit Information
Permit NumberFIR16-00337
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP Bld 8 SYKES Clean Agent
Customer Number 
ePlanReviewYes
Description
HP8 Clean Agent works is to install three(3) new fire suppression systems with AUTOPULSE 542R RELEASING PANELS in rooms 122, 214, & 312: Provide new devices as shown on drawings. Each AUTOPULSE releasing panel to be connected to and monitored by the existing building fire alarm panel. Associated with building permit BLD15-03153.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/17/20171/18/20171/18/2017APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/12/20171/13/20171/13/2017AFAIL
DetailsTroy Cobbley
Need to change the programing of the pre-action release panel to delete the 30 countdown as discussed. All other items have been tested.
INSP-Final Inspection1/9/20171/10/20171/10/2017AFAIL
DetailsTroy Cobbley
Resubmit plans showing the corrected alarm activation as per discussion and address all of the items listed in the review comments. Provide "abort" outside of the room as per review note #4. provide signage and door sweep as per discussion. Raise the first and third floor nozzles to within 12" of ceiling as per notes on plans. All three wall mounted strobes are overspaced. Provide ceiling in the first floor "releasing panel room". We need to test all of the devices. Get approval to relocate the manual pull station to the inside of the room.
INSP-Final Inspection1/3/20171/6/20171/6/2017ACANC
DetailsTroy Cobbley
As early as possible Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, January 06, 2017.