Permit Information
Permit NumberFIR16-00344
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 1055 E PARKCENTER BLVD
Project NameAlbertsons SET Store TI
Customer Number 
ePlanReviewYes
Description
[Albertsons SET Store TI]
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration, adding a new loading dock, upgrading the fire sprinkle design for the receiving area and adding sprinklers to a new open office area.

Location on Plan - Receiving
Commodity - Grocery
Classification - Class IV
Storage Type (rack, solid pile, etc.) - Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - 8’
Height of Storage - 16’
Ceiling Height - 20’±
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - K=11.2
High Temperature Sprinklers Required - Yes
Applicable NFPA Section - 16.2.1.3.2(d) Curve E, 16.2.1.3.4.1.
Hydraulic Design Criterion - .495/2000 – 65% = .325/2000
Hose Stream Requirements - 500


(ALBERTSONS - SET STORE) Add office area, store staging area, restroom core, and loading dock to existing building shell. Minor demolition of exterior wall and site to accommodate new construction.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/30/20168/31/20168/31/2016APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro8/5/20168/5/20168/5/2016PPASS
DetailsJim Page
24 hour air test for new dry system passed/complete
INSP-Sprinkler Rough-in8/5/20168/8/20168/5/2016ACANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in/Hydro8/4/20168/4/20168/4/2016PPART
DetailsJim Page
24 hour air test started at 3:00 pm.
INSP-Sprinkler Rough-in7/27/20167/28/20167/28/2016APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located above ceiling grid area's complete, overhead fire sprinkler piping located above ceiling grid area's from middle of tenant space north approved for cover.