Permit NumberFIR16-00357
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1055 N CURTIS RD
Project NameSARMC Easy Street Remodel
Customer Number 
ePlanReviewYes
Description
Easy Street Remodel SARM 4th Floor scope is to modify existing fire alarm system providing new devices, relocate and demo existing. Associated with building permit BLD16-00628.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/11/20178/14/20178/14/2017APASS
DetailsJim Page
Previously noted items have been repaired, final fire alarm inspection for area of work passed/complete.
INSP-Alarm Testing11/16/201611/17/201611/17/2016APART
DetailsTroy Cobbley
New notification devices functioned correctly in the new scope of work. The issues is the new devices do not sync with the existing devices outside of the scope of work. I contacted Ron with the Boise Fire Dept and he stated that the new and old devices will need to sync as per code requirements.
INSP-Alarm Testing10/19/201610/20/201610/20/2016APART
DetailsTroy Cobbley
For a final sign off the new notification devices need to be installed and tested. Per Scott Arellano a 30 temporary for life safety is ok until the new devices are installed and tested.
INSP-Alarm Testing10/12/201610/13/201610/13/2016ADONE
DetailsTroy Cobbley
Need to add smoke detector in the Nurses Station area, need to relocate two other smoke detectors away from air diffusers, one wall mount strobe was non-functional, audio was not temporal but march time, elevator recall was not tested or any of the new smoke detectors in the corridor system. Scott Arellano is ok with a 30 day temporary to allow time for the contractor to correct the audio as long as all other items have been corrected.