Permit Information
Permit NumberFIR16-00383
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 505 W BROAD ST
Project Name5TH & BROAD - SHELL & CORE
Customer Number 
ePlanReviewYes
Description
5th&Broad (The Fowler) core & shell scope of work is to provide and install new automatic and manual Fire Alarm System on a new building. Area of Work covers 5 live/work units, 4 future tenant spaces on the 1st floor, and accessory office/residential amenity rooms on the 2nd floor. Associated with building permit BLD15-03835.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/28/20183/1/20183/1/2018PCANC
DetailsJim Page
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A
INSP-Final Inspection3/1/20183/1/20183/1/2018PPASS
DetailsJim Page
Final fire alarm inspection complete.
INSP-Final Inspection2/28/20182/28/20182/28/2018PCANC
DetailsJim Page
As late as possible Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A Inspection cancelled via mobile web on Wednesday, February 28, 2018.
INSP-Alarm Testing2/9/20182/9/20182/9/2018PDONE
DetailsJim Page
Fire alarm testing for levels 3 and 4 complete.
INSP-Alarm Testing1/30/20181/30/20181/30/2018PDONE
DetailsJim Page
Fire alarm testing for stairwell number 2 pressurization complete.
INSP-Alarm Testing1/29/20181/29/20181/29/2018PDONE
DetailsJim Page
Fire alarm testing complete for level 1 lobby and level 2 common areas. Additional notification needed for level 1.5 southside of garage.
INSP-Alarm Testing1/26/20181/26/20181/26/2018PPART
DetailsJim Page
Fire alarm testing for levels 5 and 6 complete.
INSP-Alarm Testing1/23/20181/23/20181/23/2018PDONE
DetailsJim Page
More fire alarm testing needs to happen on level 6 before TCO
INSP-Alarm Testing1/16/20181/16/20181/16/2018PDONE
DetailsJim Page
Fire alarm inspection/testing for level 7 complete.
INSP-Alarm Testing1/9/20181/16/20181/16/2018ACANC
DetailsJim Page
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A Inspection cancelled via mobile web on Tuesday, January 16, 2018.
INSP-Alarm Testing9/18/20179/20/20179/20/2017APART
DetailsJim Page
Fire alarm testing complete for fire pump riser room/fire pump room dry systems (Parking levels 1 and 2 dry systems). All tampers and flow switches in fire pump room complete, fire pump monitoring complete, tampers and flows complete for levels 1 and 2 wet systems.
INSP-Alarm Testing9/14/20179/14/20179/14/2017PDONE
DetailsTroy Cobbley
Today I verified the panel, batteries, phone lines, phone line troubles, battery troubles and smoke detector over the panel. Most other devices have not been connected to the main fire alarm panel. I was unable to test the hood suppression system and a/v's in the Pizza tenant due to the approved plans for the space not being on site. I also pointed out the a plan modification is needed for the new devices (fire pump) and deletion of devices. Also a plan modification is needed for stair shaft pressurization as noted on the city approved fire alarm plans.