Permit Information
Permit NumberFIR16-00460
StatusFinaled
Name MOUNTAIN ALARM
Site Address 1055 E PARKCENTER BLVD
Project NameAlbertsons Set Store
Customer Number 
ePlanReviewYes
Description
Expansion of current fire alarm system (Gordman's) to replace fire devices removed in demolition of old (KMart) space. Associated with building permit BLD16-01406.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/1/20169/2/20169/2/2016APASS
DetailsJim Page
Previously noted items have been repaired/addressed, final fire alarm inspection passed/complete.
INSP-Final Inspection8/30/20168/31/20168/31/2016AFAIL
DetailsTroy Cobbley
Resubmit plans showing the wire guage change, added strobes, changed candellas. Plans need to address the different NAC panel. I did test the sync which was ok. I did test the interconnection with the new dry pipe riser which was ok. I did not test the duct smoke detectors. Per general contractor security is being installed on the doors but will not hinder exiting in a single motion.
INSP-Final Inspection8/29/20168/31/20168/30/2016PCANC
DetailsJim Page
Location Access: site is open
Installation Technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson