INSP-Final Inspection | 10/11/2016 | 10/11/2016 | 10/11/2016 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection passed/complete
|
INSP-Sprinkler Rough-in | 10/11/2016 | 10/11/2016 | 10/11/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping complete.
|
INSP-Sprinkler Rough-in | 9/22/2016 | 9/23/2016 | 9/23/2016 | A | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover. Pendant head located in the dining area is less than 12 inches from heat source grid mounted heat register, sprinkler head will be changed from a 155 degree to a 200 degree.
|