Permit Information
Permit NumberFIR16-00586
StatusFinaled
Name DELTA FIRE SYSTEMS
Site Address 2950 E PARKCENTER BLVD
Project NameArboretum at Barber Station
Customer Number 
ePlanReviewYes
Description
[Arboretum at Barber Station]
The fire sprinkler scope of work consists of Building #1 only. The five level building is protected per NFPA 13. The bottom level is a parking garage. The remaining levels are residential. The 6” underground will supply a 6” backflow preventer and 6” header. There is a dry system for the basement and a wet system for the remainder of the floors. There are two wet standpipes. One standpipe is being used as a combination riser for the floor control valves.

The underground piping is under permit FIR16-00473

[BLD16-01058] - (Building #1) Permit to construct a new 121,503 square foot (5) story apartment building. First floor foundation and concrete podium permit submitted under BLD15-04472. Each floor is approximately 24,176 square feet. Approval contingent upon adhering to the approved plans on file and attached engineering. This building is fully fire sprinklered with an NFPA 13 system to comply with special provisions of section 510.2 and area increase. Scope of work includes: interior finish of the first floor, construction of wood frame 4 story building on top of the previously approved podium, installation of interior non-bearing walls and bearing walls to create 76 individual units, new plumbing, new electrical, new mechanical, new insulation, new windows, new doors, and interior finishes in compliance with Chapter 8 of the 2012 IBC. This building will be sprinklered with special provisions of section 510.2 and area increase. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/24/20184/26/20184/26/2018APASS
DetailsJim Page
Final fire sprinkler inspection complete.
INSP-Sprinkler Rough-in/Hydro4/24/20184/26/20184/26/2018ADONE
DetailsJim Page
Hydrostatic test for levl 4 wet system witnessed, no pressure loss observed at rised provided gauge.
INSP-Final Inspection4/18/20184/23/20184/23/2018APART
DetailsJim Page
Fire sprinkler heads/escutcheons on levels 5, 3, and 2 are complete, still need to test flow switches/tampers on all floors.
INSP-Sprinkler Rough-in/Hydro4/23/20184/23/20184/23/2018AFAIL
DetailsJim Page
Hydrostatic test for level 4 will need to be completed after repairs are made. Relocate heads that are blocked by drain piping on level 1 dry system.
INSP-Sprinkler Rough-in/Hydro4/18/20184/20/20184/20/2018PPART
DetailsJim Page
Hydrostatic test witnessed for southeast wet standpipe, levels 2, 3 and 5, no pressure observed at contractor supplied gauges. Level 4 still needs to have hydro completed.
INSP-Sprinkler Rough-in10/27/201710/30/201710/30/2017ADONE
DetailsTroy Cobbley
Duplicate inspection work an inspection I performed on Fridayl.

Tenting of sprinkler lines in units 509-519 passed. Numerous corrections made while I was on site.
INSP-Sprinkler Rough-in10/27/201710/27/201710/27/2017PPASS
DetailsTroy Cobbley
Tenting of sprinkler lines in units 509-519 passed. Numerous corrections made while I was on site.
INSP-Sprinkler Rough-in10/24/201710/25/201710/25/2017AFAIL
DetailsJim Page
Overhead fire sprinkler piping is covered in numerous areas, a clear pocket must be maintained between sheetrock and fire sprinkler piping for radiant heat to reach pipe. Overehad fire sprinkler piping north of the e;evator lobby is not approved for cover.
INSP-Sprinkler Rough-in/Hydro9/22/20179/22/20179/22/2017PPASS
DetailsJim Page
24 hour air test complete
INSP-Sprinkler Rough-in9/21/20179/21/20179/21/2017PPART
DetailsJim Page
24 hour air test started with 50psi at 2:00pm
INSP-Sprinkler Rough-in9/7/20179/8/20179/8/2017APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping north of elevator on level 4 complete, level 4 north of elevator approved for cover.
INSP-Sprinkler Rough-in8/29/20178/30/20178/30/2017APART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping on the remainder of level 5 complete (North of elevator shaft) insulation/tenting still needs to be installed, cover is not approved until tenting inspection is complete.
INSP-Sprinkler Rough-in8/16/20178/17/20178/17/2017APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/tenting on level 5 south of the elevator shate complete, level 5 south of elevator shaft approved for cover.
INSP-Sprinkler Rough-in8/16/20178/16/20178/16/2017PCANC
DetailsJim Page
Inspection request rescheduled for 17AUG2017, this request is cancelled
INSP-Sprinkler Rough-in8/9/20178/9/20178/9/2017PPART
DetailsJim Page
Rough to cover inspection for south side of elevator lobby, level 4 overhead fire sprinkler piping/pendant heads complete, inspected area on level 4 approved for cover, north of elevator to be completed/inspected at a later date. Rough in inspection for south side level 5 complete, cover is not approved until insulation is installed over piping and passed inspection. North side of elevator on level 5 to be completed/inspected at a later date.
INSP-Sprinkler Rough-in7/27/20177/27/20177/27/2017PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping on level 3 complete, level 3 approved for cover.
INSP-Sprinkler Rough-in7/12/20177/13/20177/13/2017APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping on level 2 complete, level 2 approved for cover.
INSP-Sprinkler Rough-in/Hydro6/29/20176/29/20176/29/2017APART
DetailsJim Page
Hydrostatic test for wet standpipe and parking level complete.