Permit Number | FIR16-00806 |
Status | Finaled |
Name |
TREASURE VALLEY FIRE PROTECTION
|
Site Address |
12463 W FAIRVIEW AVE
|
Project Name | MAVERICK CAR COMPANY |
Customer Number | |
ePlanReview | Yes |
Description |
[Maverick Car Company]
The fire sprinkler scope of work consists of a wet system protecting a one level building with a mezzanine. The mezzanine is Light hazard and the remainder of the building is OH 2. The 6” underground supplies a 3” backflow preventer and riser to a 2 ½” x2”x1 ½” grid. The mezzanine is a side feed design with 2 ½” main and telescoping branch lines.
? There is to be NO flammable finish operations without a complete new fire sprinkler review.
The underground piping is under permit FIR16-00712
[BLD16-02889] – Permit for the construction of a new 6,119 Sq. Ft. 1 story with a 945 sq. ft. mezzanine, 5,530 grade level and 539 sq. ft. of covered parking building areas include office, showroom, exterior covered parking , and a car detailing shop with work to include site grading and utilities and the construction of a new steel building. this building is fully fire sprinklered to allow for the larger mezzanine and common path of travel of 100 feet. CDM
|