Permit Information
Permit NumberFIR16-00822
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 1387 S VINNELL WAY
Project NameBLM 3rd Floor TI
Customer Number 
ePlanReviewYes
Description
[BLM 3rd Floor - Suite 301] - Quick Permit
Add and relocate sprinklers as required based on new walls in this existing office space on the existing fire sprinkler system.

[BLD16-04264] - Permit is to remodel west end within the 13,400 sq. ft. third floor of an existing building. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls, removal of select door/door frames, construction of select interior nonbearing walls and select wall infill to create (7) offices, a storage room and a conference room, select new door/door frames, relocate existing light fixtures, electrical work, mechanical work and interior finishes to be in compliance with Ch. 8 of the 2012 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/28/20172/28/20172/28/2017APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in1/31/20172/1/20172/1/2017APASS
DetailsKatie Marron
Phase 2 rough-in completed. OK to cover.
Walked through new extinguisher placement, two new extinguisher to be placed.
INSP-Sprinkler Rough-in1/4/20171/5/20171/5/2017APASS
DetailsTroy Cobbley
The phase 1 sprinkler piping is ok to cover. I noted one overspaced head in a office where the 9' rule is being used off of two walls which is not allowed. I will verify it has been fixed at the next inspection. Piping is ok to cover.
INSP-Sprinkler Rough-in1/4/20171/4/20171/4/2017PFAIL
DetailsTroy Cobbley
No inspection was performed due to signage on building door stating the building was shut due to weather