Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR17-00027
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 5710 S PAN AM AVE
Project NameSysco Food - Overflow Racking
Customer Number 
ePlanReviewYes
Description
[Sysco Food - Overflow Racking]
The fire sprinkler scope of work consists of adding one row of in rack sprinklers,
Location on Plan -
Col 4 between Col C & E
Commodity -
Water filled bottles wrapped in plastic, canned Foods on cardboard wrapped in plastic and flour in paper bags in plastic
Classification -
Storage Type (rack, solid pile, etc.) -
Racks
Pallet Type (wood or plastic) -
Wood
Aisle Width -
One Row ONLY – No Aisle
Height of Storage -
22’
Ceiling Height -
25’-8”
Encapsulated -
No
Solid Shelves -
No
Smoke and Heat Vents -
No
Draft Curtain -
No
In Rack Sprinklers -
Yes
Sprinkler Type -
Existing 100 ft² .19/2009 (21) Flowing
High Temperature Sprinklers Required -
Yes
Applicable NFPA Section -
16.2.1.3.2(c) curve A or B
Hydraulic Design Criterion -
.245/2000
Hose Stream Requirements -
500
There does not seem to be an associated building permit at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in4/7/20174/7/20174/7/2017PPASS
DetailsScott Arellano
Please call me about 45 min before you will be there. The job is in east boise and I am in Meridian so it''ll take me a minute to get there. Thanks, Brett Phone #: ###-#### Inspection requested via web by Brett Lawatch
INSP-Final Inspection4/7/20174/7/20174/7/2017PPASS
DetailsScott Arellano
Please call me about 45 min before you will be there. The job is in east boise and I am in Meridian so it''ll take me a minute to get there. Thanks, Brett Phone #: ###-#### Inspection requested via web by Brett Lawatch