Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR17-00178
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project NameC24074 B51 R & D Expansion
Customer Number 
ePlanReviewYes
Description
C24074 B51 R & D Expansion is a 100,000sf. free standing expansion of Microns Research and Development Facilities, and an extension of the previously constructed B50. Associated with building permit BLD16-03440.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/30/20207/31/20207/31/2020APASS
DetailsJim Page
Final fire alarm inspection is complete.

Screened- Dillon Phone #: ###-####
INSP-Final Inspection5/20/20205/21/20205/21/2020APART
DetailsJim Page
Final fire alarm inspection for pyrophoric building is complete, fire alarm permit covers entire B51 building to include pyrophonic building, fire alarm permit will remain in issued status until entire FIR permit scope is inspected.

Dillin *screened* Phone #: ###-####
INSP-Alarm Testing4/27/20204/27/20204/27/2020PDONE
DetailsTroy Cobbley
I helped Jim Page out on this inspection. Please see the city approved plans for corrections notated.
INSP-Alarm Testing4/24/20204/27/20204/27/2020APART
DetailsJim Page
Fire alarm walkthrough partially complete, city approved plans have been notated for areas to correct.

screened // Dillon Phone #: ###-####
INSP-Alarm Testing4/23/20204/24/20204/24/2020APART
DetailsJim Page
Fire alarm walkthrough partially complete, city approved plans have been notated for areas to correct.

*screened* Dillon Phone #: ###-####
INSP-Alarm Testing4/22/20204/23/20204/23/2020APART
DetailsJim Page
Walk through for level 3 complete, notated city approved drawings areas needing correction, 4 areas total for level 3.

dillon Phone #: ###-####
INSP-Final Inspection1/10/20201/13/20201/13/2020AFAIL
DetailsJim Page
Overspaced audio visual devices in electrical room area, section 10 area 90. Notated city approved draiwngs areas where candella setting was incorrect, inspection was stopped after 6 deficiencies.

Dillion Phone #: ###-####
INSP-Final Inspection1/8/20201/10/20201/10/2020ACANC
DetailsJim Page
Coordinated for 13JAN2020, cancelled due to inspection load and time required for this inspection.

Dillion Phone #: ###-####
INSP-Final Inspection12/19/201912/20/201912/20/2019PPART
DetailsJim Page
FIre alarm inspection for TCUP is complete, fire alarm system in TCUP is compliant with NFPA 72, Due to this system being included in the B51 plans, Fire Alarm Plan Examiner still needs to perform review, per conversation with Joe Bruce, Fire Section Supervisor, if fire alarm system is compliant with NFPA 72 then life fire safety inspection can be performed due to the TCUP being included on the B51 drawings. Will verify that install matches submittal during B51 inspection.

.tea cup // Dillon Phone #: ###-####
INSP-Alarm Testing10/22/201910/22/201910/22/2019AFAIL
DetailsJim Page
Started inspection in level 10, section 90 of the city approved drawings, notated 7 areas that need corrected where candella settings due not match what was submitted as well as a/v devices that have been added that are not on city approved drawings, inspection stopped due to defecincies noted.

Requesting for 10/22 AM
INSP-Alarm Testing10/21/201910/21/201910/21/2019PCANC
DetailsTroy Cobbley
To be rescheduled per paul ###-####
INSP-Final Inspection10/8/201910/9/201910/9/2019ACANC
DetailsJim Page
Dillon Phone #: ###-####
INSP-Alarm Testing11/7/201711/8/201711/8/2017PPART
DetailsJim Page
Fire alarm testing/inspection for TCUP building complete.
INSP-Conference10/23/201710/23/201710/23/2017PDONE
DetailsJim Page
Discuss requirements for passenger elevator control room/and shaft.
Currently the elevator controller is in the shaft space. There are no walls or hard lid that separate the controller and the shaft. Top of the shaft is 60ft above controller. Device maintenance is a concern.
Tribal Fire also questions the location of the sprinkler heads needed.


Issue is deferred to fire alarm system design and plan review to provide a solution.
INSP-Alarm Testing10/10/201710/11/201710/11/2017ADONE
DetailsJim Page
Audio visual notification for Building 51.2 sections complete. Fire riser monitoring for area's associated with building 51.2 complete.
INSP-Alarm Testing7/11/20177/12/20177/12/2017PDONE
DetailsJim Page
Alarm testing for deluge system associated with this permit complete.
INSP-Alarm Testing6/29/20176/30/20176/30/2017PPART
DetailsJim Page
Fire alarm testing for fire sprinkler risers protecting TCO requested area complete, audio visual device testing for TCO requested area complete to include clean room area.
INSP-Alarm Testing6/27/20176/29/20176/29/2017PCANC
DetailsJim Page
Inspection request cancelled per conversation with Toby Phone #: ###-#### Inspection requested will be rescheduled.