INSP-Final Inspection | 8/28/2018 | 8/29/2018 | 8/29/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Rafe Phone #: ###-####
|
INSP-Final Inspection | 8/2/2018 | 8/3/2018 | 8/3/2018 | P | CANC |
Troy Cobbley
|
|
|
Rafe Phone #: ###-####
|
INSP-Final Inspection | 4/30/2018 | 5/1/2018 | 5/1/2018 | A | FAIL |
Troy Cobbley
|
|
|
Provide as-builts with the candella changes and the revised zones. Provide adjustment for the tamper switches, provide supervisory signal to the monitoring agency.
6:30 am inspection // Rase Phone #: ###-####
|
INSP-Final Inspection | 4/19/2018 | 4/20/2018 | 4/20/2018 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for corrections needed. No actual testing performed.
Rafe Phone #: ###-####
|
INSP-Final Inspection | 4/10/2018 | 4/12/2018 | 4/12/2018 | P | CANC |
Troy Cobbley
|
|
|
Rafe Phone #: ###-####
|
INSP-Final Inspection | 2/5/2018 | 2/15/2018 | 2/15/2018 | P | FAIL |
Troy Cobbley
|
|
|
For todays inspection we did a walk through for the placement of the notification devices. No actual testing was performed due to numerous corrections needed and no small documents available on site. I noted the manual pull stations are not mounted at the correct heights and one manual pull station has not been relocated yet as shown on the plans. Several strobes are overspaced and there are many locations where additional notification devices will be required. These locations include rooms marked as "offices" but are actually set up with functioning medical equipment. Also the floor plan/wall layout does not match in all locations. It appears plan modifications are required prior to the next inspection.
Rafe Phone #: ###-####
|