Permit Information
Permit NumberFIR17-00282
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 607 N 8TH ST
Project NamePERSI Bldg 4th Floor TI
Customer Number 
ePlanReviewYes
Description
[PERSI Building 4th Floor TI]
Add 5 new 5.6 pendent sprinklers and change 53 existing 5.6 upright shell lers into 53 new 5.6 pendent sprinklers for tenant improvement on 4th floor of Class II B building.

[BLD17-00639] -Permit is to remodel an existing 8,025 sq. ft. business space on the whole fourth floor. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls, construction of interior non-bearing walls to create (10) offices, a storage room, (2) copy rooms, a break room, (3) conference rooms, an open office area, a reception area and a waiting area, new door/door frames, select new millwork, select new gypsum ceiling, select new acoustic ceiling, new light fixtures, electrical work, mechanical work and interior finishes on the 3rd and 4th floor in compliance with Ch. 8 of the 2012 IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/17/20178/17/20178/17/2017APASS
DetailsJim Page
Final fire sprinkler inspection for area of work passed/complete
INSP-Final Inspection8/14/20178/16/20178/16/2017AFAIL
DetailsJim Page
Fire sprinkler head in northwest corridor next to handwash sink, electrical closets is overspaced. Sprinkler head above handwash sink needs to be changed to a quick response head. Fire sprinkler heads located in level 4 elevator lobby need to be changed to quick response heads.
INSP-Sprinkler Rough-in8/2/20178/3/20178/3/2017PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/pendant heads complete in area of work, area of work approved for cover.
INSP-Sprinkler Rough-in6/28/20176/29/20176/29/2017APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/pendant heads located above hardlids complete, approved for cover.