Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR17-00350
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 607 N 8TH ST
Project NamePERSI BUILDING 4TH FLOOR
Customer Number 
ePlanReviewYes
Description
PERSI BUILDING 4TH FLOOR scope of work is to add notification devices and relocate existing smoke detectors to meet code. We are adding a new NAC panel to be triggered from existing NAC circuit in the floor. Adding one duct detector tie to the duct detector zone in the Penthouse floor above. This work is associated with building permit BLD17-00639.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/17/20178/17/20178/17/2017APASS
DetailsJim Page
Area of work does have active fire alarms throughout tenant space, audio alarms do not have 3 temporal throughout space. Contractor is working with building manager/property owners to upgrade fire alarm system upgrade to address notification issues. Final fire alarm inspection for this area of work complete, any other future work throughout building that occurs and fire alarm issues are not resloved will result in an inspection failure.