Permit Information
Permit NumberFIR17-00364
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 8800 W EMERALD ST
Project NameTREASURE VALLEY HOSPITAL ADDIT
Customer Number 
ePlanReviewYes
Description
TREASURE VALLEY HOSPITAL ADDITION scope of work is to add initiation and notification devices thru numerous areas of remodel. New Simplex 4010ES panel to network with existing Simplex 4010ES FACP. Adding new Annunciators, NAC panel, sprinkler monitoring, damper and AHVC system control. Kitchen Hood monitoring, Door releasing and security door unlock. This work is associated with building permit BLD17-01088.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/14/20188/15/20188/15/2018PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/20/20187/23/20187/23/2018AFAIL
DetailsTroy Cobbley
Waiting on as-builts to be submitted/approved then this permit can be finaled

Rafe Phone #: ###-####
INSP-Final Inspection7/23/20187/23/20187/23/2018AFAIL
DetailsTroy Cobbley
The new smoke detector failed to operate. Still need as-builts.
INSP-Final Inspection7/19/20187/20/20187/20/2018AFAIL
DetailsTroy Cobbley
Need as-builts, need smoke detector in existing corridor, need additional strobe in Pharmacy.

Rafe Phone #: ###-####
INSP-Alarm Testing4/16/20184/16/20184/16/2018PDONE
DetailsJim Page
Fire alarm testing for room 118 complete
INSP-Final Inspection3/12/20183/12/20183/12/2018APART
DetailsJim Page
Partial final inspection complete for fire alarm system, notated city approved drawings with red ink areas that have been finaled.
INSP-Alarm Testing3/9/20183/12/20183/12/2018ADONE
DetailsJim Page
Notated city approved drawings where testing is complete.
INSP-Alarm Testing12/12/201712/12/201712/12/2017PDONE
DetailsTroy Cobbley
Alarms complete in MOB but flow switch for the new sprinkler system covering the addition (connecting corridor) was not ready.

Call prior to going Phone #: 2085190509 >> Inspection requested via mobile web by Raff
INSP-Alarm Testing12/9/201712/11/201712/11/2017APART
DetailsJim Page
Alarm testing/inspection complete for HVAC unit shutdown, HVAC units reported to panel. Audio visual notification is complete, smoke detector testing complete. Smoke detector next to dishwasher was changed to a heat detector, panel programing will be completed before next inspection request. Door holders and flow switches still need to be tested/inspected.
INSP-Final Inspection11/24/201711/27/201711/27/2017APART
DetailsTroy Cobbley
The fire alarm work/testing is complete for the new Pharmacy Rooms in the existing hospital. An additional chime was added.

Rafe Phone #: ###-####
INSP-Alarm Testing11/21/201711/22/201711/22/2017AFAIL
DetailsTroy Cobbley
Todays inspection was for the Pharmacy Rooms. A chime needs to be added to meet sound requirements prior to work being completed in this area.
INSP-Alarm Testing10/2/201710/2/201710/2/2017PPART
DetailsTroy Cobbley
The fire alarm system/devices for OR 141 passed.

Damon Phone #: ###-####