INSP-Final Inspection | 8/14/2018 | 8/15/2018 | 8/15/2018 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 7/20/2018 | 7/23/2018 | 7/23/2018 | A | FAIL |
Troy Cobbley
|
|
|
Waiting on as-builts to be submitted/approved then this permit can be finaled
Rafe Phone #: ###-####
|
INSP-Final Inspection | 7/23/2018 | 7/23/2018 | 7/23/2018 | A | FAIL |
Troy Cobbley
|
|
|
The new smoke detector failed to operate. Still need as-builts.
|
INSP-Final Inspection | 7/19/2018 | 7/20/2018 | 7/20/2018 | A | FAIL |
Troy Cobbley
|
|
|
Need as-builts, need smoke detector in existing corridor, need additional strobe in Pharmacy.
Rafe Phone #: ###-####
|
INSP-Alarm Testing | 4/16/2018 | 4/16/2018 | 4/16/2018 | P | DONE |
Jim Page
|
|
|
Fire alarm testing for room 118 complete
|
INSP-Final Inspection | 3/12/2018 | 3/12/2018 | 3/12/2018 | A | PART |
Jim Page
|
|
|
Partial final inspection complete for fire alarm system, notated city approved drawings with red ink areas that have been finaled.
|
INSP-Alarm Testing | 3/9/2018 | 3/12/2018 | 3/12/2018 | A | DONE |
Jim Page
|
|
|
Notated city approved drawings where testing is complete.
|
INSP-Alarm Testing | 12/12/2017 | 12/12/2017 | 12/12/2017 | P | DONE |
Troy Cobbley
|
|
|
Alarms complete in MOB but flow switch for the new sprinkler system covering the addition (connecting corridor) was not ready.
Call prior to going Phone #: 2085190509 >> Inspection requested via mobile web by Raff
|
INSP-Alarm Testing | 12/9/2017 | 12/11/2017 | 12/11/2017 | A | PART |
Jim Page
|
|
|
Alarm testing/inspection complete for HVAC unit shutdown, HVAC units reported to panel. Audio visual notification is complete, smoke detector testing complete. Smoke detector next to dishwasher was changed to a heat detector, panel programing will be completed before next inspection request. Door holders and flow switches still need to be tested/inspected.
|
INSP-Final Inspection | 11/24/2017 | 11/27/2017 | 11/27/2017 | A | PART |
Troy Cobbley
|
|
|
The fire alarm work/testing is complete for the new Pharmacy Rooms in the existing hospital. An additional chime was added.
Rafe Phone #: ###-####
|
INSP-Alarm Testing | 11/21/2017 | 11/22/2017 | 11/22/2017 | A | FAIL |
Troy Cobbley
|
|
|
Todays inspection was for the Pharmacy Rooms. A chime needs to be added to meet sound requirements prior to work being completed in this area.
|
INSP-Alarm Testing | 10/2/2017 | 10/2/2017 | 10/2/2017 | P | PART |
Troy Cobbley
|
|
|
The fire alarm system/devices for OR 141 passed.
Damon Phone #: ###-####
|