Permit Information
Permit NumberFIR17-00372
StatusFinaled
Name ALARMCO
Site Address 9300 W OVERLAND RD
Project NameLynx Building
Customer Number 
ePlanReviewYes
Description
Addition of one horn strobe on the first floor in suite 9328. This work is associated with building permit BLD17-01670.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/24/20177/24/20177/24/2017PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/19/20177/20/20177/20/2017APART
DetailsTroy Cobbley
Permit can be finaled when Lee has received the as-builts. Jeremy will re-schedule for monday final
INSP-Final Inspection7/17/20177/18/20177/18/2017PFAIL
DetailsTroy Cobbley
No testing performed. Need strobe coverage modified for the entire space including short corridor and restroom. As-builts to both plan review and myself is ok.