Permit NumberFIR17-00426
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 3501 W ELDER ST Unit: 200
Project NameLitster Frost TI
Customer Number 
ePlanReviewNo
Description
Permit to add 2 new a/v devices and relocate 1 within an existing office space. Each new device is on separate notification applianc circuits (NAC) and battery calcs have been provided supporting these additional devices. Final approval will be subject to satisfactory field inspection and functional test of each NAC.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/14/20178/14/20178/14/2017PPASS
DetailsJim Page
Previously noted items have been addressed/repaired. Final fire alarm inspection for area of work passed/complete.
INSP-Final Inspection8/11/20178/11/20178/11/2017PFAIL
DetailsTroy Cobbley
As-builts are needed showing all of the audio/visual devices and the accurate location of all devices. Coverage needs to be modified in two corridors and coverage provided in the other half of the Conference Room.