Permit Information
Permit NumberFIR17-00444
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 12754 W LASALLE ST
Project NameSEL Notification Upgrade
Customer Number 
ePlanReviewYes
Description
Current facility has no audible or visual notification. Upgrade will cover all common areas and corridors with A/V notification. Appliances to be powered by a new 6 amp power extender panel triggered by the existing FACP NAC circuit. Existing FACP is a basic riser monitor. During the upgrade, a pull station will be added at the receptionist's desk for manual activation of system.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/20/20179/22/20179/22/2017APASS
DetailsJim Page
As-builts are complete, final fire alarm inspection passed/complete.
INSP-Final Inspection9/13/20179/15/20179/15/2017AFAIL
DetailsTroy Cobbley
Not all items tested today. I verified the battery trouble and output circuit trouble from the NAC panel. I noted many of the 15cd strobes are mounted above 10'. Since candella will be changes as-builts will need to be provided to myself and plan review showing the changes. John Phone #: ###-####
INSP-Final Inspection9/13/20179/13/20179/13/2017PCANC
DetailsJim Page
Inspection request cancelled per conversation with John Howard Phone #: ###-####, Inspection will be rescheduled for a later date.