Permit NumberFIR17-00521
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 6434 W GOWEN RD
Project NameVermeer Rocky Mountain TI
Customer Number 
ePlanReviewYes
Description
[Vermeer Rocky Mountain TI] - Quick Permit
Install 3 new pendent sprinklers, relocate 13 pendent sprinklers, plug 1 sprinkler drop, and change out 3 existing pendent sprinklers to match the new sprinklers, due to new walls in this tenant improvement space.

[BLD17-02707]
Build a new Vermeer Rocky Mountain showroom and parts room area and upgrade of finishes in existing office area
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/20/201712/20/201712/20/2017APASS
DetailsTroy Cobbley
Permit finaled

Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in12/4/201712/4/201712/4/2017PPASS
DetailsTroy Cobbley
The upright sprinklers have been added at draft stop. Piping is ok for cover.

Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in11/27/201711/29/201711/29/2017PPART
DetailsTroy Cobbley
Rough-in as per the scope of work is complete but I noted additional upright sprinkler coverage is required due to a draft stop in the attic space. Piping is ok to cover but I will need access to verify the additional uprights prior to a final.