INSP-Final Inspection | 11/8/2017 | 11/9/2017 | 11/9/2017 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The fire alarm plans address was incorrect. Address has been changed to match the building address
|
INSP-Final Inspection | 10/30/2017 | 11/1/2017 | 11/1/2017 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Jeremy Phone #: ###-####
|
INSP-Final Inspection | 10/26/2017 | 10/27/2017 | 10/27/2017 | A | FAIL |
Troy Cobbley
|
|
|
Not ready for final due to the PIV not reporting correctly and I noted alot of the notofication devices are overspaced and the area behind the front counter has no coverage. No actual testing performed. I went over items with the tech. Plans are too small to read and do not show the communication means being used. As-builts or possibly plan modifications are needed.
Jeremy Berg Phone #: ###-####
|