INSP-Final Inspection | 9/20/2018 | 9/21/2018 | 9/21/2018 | A | PASS |
Lee G Meredith
|
|
|
Gerry from Colliers is verifying that we will have access to tenant spaces, for example the daycare, H&R Block, and ice cream shop. Meet with Peter from Crane Alarm. Please call the office at ###-#### prior to inspection with a firm time. Thank you. Phone #: ###-#### >> Inspection requested via web by Laura Tyson
|
DOC - Permit Finaled | | | 9/21/2018 | | DONE |
|
|
|
Duct detection / shutdown and notification tested and approved.
|
INSP-Final Inspection | 4/4/2018 | 4/6/2018 | 4/6/2018 | A | FAIL |
Troy Cobbley
|
|
|
The head end equipment was tested. Netcon was a 5. Batteries match and a dedicated circuit has been provied. No sprinkler devices have been tested due to the sprinkler contractor not showing up. We tested duct smoke detectors in multiple tenant spaces and I noted in one space the duct smoke detector did not shut down immediatley as required. Also plan modifications are needed to show the notification devices in the two riser rooms and through out the day care. The ground wire for the AES has not been installed either.
Laura -call for access--owner and Jim from American Fire, and keith, colliers, peter from crane alarm Phone #: ###-####
|