INSP-Final Inspection | 8/6/2018 | 8/6/2018 | 8/6/2018 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
INSP-Final Inspection | 8/1/2018 | 8/2/2018 | 8/2/2018 | A | CANC |
Troy Cobbley
|
|
|
As-builts have not been provided to plan review yet.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
INSP-Final Inspection | 7/12/2018 | 7/13/2018 | 7/13/2018 | P | PART |
Troy Cobbley
|
|
|
Temporary being given until as-builts submitted/approved showing the address changes, deleting PIV and deleting tamper at the knox box.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
INSP-Final Inspection | 7/10/2018 | 7/12/2018 | 7/12/2018 | P | FAIL |
Troy Cobbley
|
|
|
See city approved plans for audio/visual devices that are overspaced. Voice evac message is not functional in the new area or the existing gym. Tamper switches wired backwards. Devices are missing. Inspection stopped until all corrections have been made and system has been pre-tested.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|