Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR17-00708
StatusFinaled
Name ROTH HOMES
Site Address 140 W SKYLARK DR
Project NameRoth Homes
Customer Number 
ePlanReviewYes
Description
[Roth Homes]
The fire sprinkler scope of work consists of protecting a 2 level single family dwelling with a NFPA 13D multipurpose system. The piping is PEX with residential sprinklers.

[BLD16-02440]
WUI Zone A; **Special inspections required, see form #310** This structure is required to be fire sprinklered in accordance with NFPA 13D** Permit for the construction of a new 4,770 sq. ft., two story (lower level1,836 sq. ft., upper level 2,934 sq. ft.) single family dwelling with 3 bedrooms, 2 full bathrooms & 2 half bathrooms, approximately 856 sq. ft. of covered patio/porch and a 757 sq. ft. attached garage per the approved plans, engineering, ACCA report and any notations. A separate fire sprinkler permit will be required. Fire/life safety inspection required for turf grass installation; ref approval under CFH16-00020. R-1B zoning and setbacks per planning.//leg ***A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection.


Alternative Materials and Methods:

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/29/20198/29/20198/29/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection complete.

INSP-Final Inspection7/26/20197/29/20197/29/2019PFAIL
DetailsJim Page
Fire sprinkler head needs to be added corridor next to glass doors.

Cleve Phone #: ###-####
INSP-Sprinkler Rough-in1/7/20191/7/20191/7/2019PFAIL
DetailsJim Page
Sprinklers need adjusted so the escutcheons fit tight against ceiling. Fire sprinkler heads need to be added in little entry to room behind kitchen with sliding glass doors as well as corridor next to glass doors.

Phone #: ###-#### Inspection requested via web by Todd Walter
FIR-Aging Inspection11/5/201811/6/201811/6/2018AFAIL
DetailsTroy Cobbley
Rings have been provided around the pendant heads which need approval from the manufacture. Need warning signs at the riser as per the approved plans. Flow switch functioned and rang the outside alarm bell.

Todd Phone #: ###-####
INSP-Final Inspection11/2/201811/5/201811/5/2018ACANC
DetailsTroy Cobbley
Todd wants to reschedule for tomorrow when he has fittings to set off the flow switch.Todd Phone #: ###-####
INSP-Sprinkler Rough-in1/16/20181/17/20181/17/2018PPASS
DetailsJim Page
Tenting inspection complete, overhead fire sprinkler piping approved for cover.
INSP-Sprinkler Rough-in1/16/20181/16/20181/16/2018PCANC
DetailsJim Page
Tenting inspection request scheduled for th wrong day, this reuqest is cancelled per conversation with installing contractor on job site.
INSP-Sprinkler Rough-in1/5/20181/5/20181/5/2018PPART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping/pendant heads complete, areas where piping is between conditioned spaces approved for cover, areas where piping is in attic spaces and requires tenting not approved for cover. Tenting needs to be installed and inspected before cover is approved.