Permit Information
Permit NumberFIR17-00716
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 505 W IDAHO ST
Project Name5th and Idaho
Customer Number 
ePlanReviewYes
Description
This is a new building in which a Kidde FX1000 Fire Alarm
Control Panel is being installed to monitor all initiating devices
and provide temporal 3 audible notification as shown. Visible
notification is in public mode. This is an addressable system.
The system is to be monitored by Apex Integrated Security, Inc. This work is associated with building permit BLD16-02008.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/25/20191/25/20191/25/2019PPASS
DetailsLee G Meredith
All systems tested 11/14/18. Issues with sync on that date were resolved by Steve Bingham PE performance testing that has since been approved on 1-25-19 by Ron Johnson.
DOC - Permit Finaled  1/25/2019 PASS
DetailsLee G Meredith
INSP-Alarm Testing11/14/201811/14/201811/14/2018AFAIL
DetailsLee G Meredith
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
On site 9:30 am with Nathan. Tested unit detectors and sounder for floors 2 - 5. Rooms requiring retest include 207,8,9,16, 315, 408, 503 and 506. Still to test is general alarm notification, corridor detection, manual alarm, all devices on 1st floor and garage, elevator recall and shunt, central station monitoring and batteries. Room on 1st floor is missing a pull box cover. Waterflow devices are missing covers.

On site 4:30 - 7:00 pm with Nathan and Adam Bayne. All remaining items tested and functioned. During general alarm, dwelling unit audible notificaiton did not sync with common area audible notificaiton. 11-15-18 discussed this issue with Ron Johnson.
INSP-Alarm Testing11/12/201811/13/201811/13/2018AFAIL
DetailsLee G Meredith
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price

System not ready. Items tested were not consistently working properly.