Permit Information
Permit NumberFIR17-00727
StatusFinaled
Name INTEGRATED SECURITY RESOURCES
Site Address 2300 S APPLE ST
Project NameALB 4602 169FC
Customer Number 
ePlanReviewYes
Description
Provide sprinkler monitoring and full notification for a new Albertson's Fuel Center / Convince Store. This work is associated with building permit BLD17-01581
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/14/201712/14/201712/14/2017PPASS
DetailsJim Page
Final fire alarm inspection complete, as-builds will be submitted for modifications that were made to system.
INSP-Final Inspection12/13/201712/14/201712/14/2017AFAIL
DetailsTroy Cobbley
Panel and devices passed, smoke and pull tested ok, phone lines tested ok, the 30cd ceiling mount near the facp needs to be relocated or adjusted to a 75cd, a strobe needs to be added in the area just outsside of the facp, as-builts are needed to show these changes, sprinkler devices not tested due to no sprinkler contractor on site. Randy is going to email verification of the signals sent.

FIR17-00727 Phone #: ###-#### Inspection requested via web by Bruce Sullivan