Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR18-00010
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 10539 W OVERLAND RD
Project NameTrade Viet Market
Customer Number 
ePlanReviewYes
Description
Update existing fire alarm system to comply with current NFPA 72 and IFC. Add full notification. Add remote test switches to all existing duct detectors. Move duct detectors to return side. Move pull station to riser room. Add a module to monitor the new Ansul suppression system. This work is associated with building permit BLD17-03838.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/26/20181/29/20181/29/2018APASS
DetailsTroy Cobbley
Permit finaled

Call prior to going Phone #: 6810381 >> Inspection requested via mobile web by Doug Lessa
INSP-Final Inspection1/25/20181/26/20181/26/2018AFAIL
DetailsTroy Cobbley
Provide modification to the two strobes to provide coverage as discussed and marked on the plans. Provide proper placement of the duct smoke detectors as discussed and provide testing. The hood suppression system reported as alarm to the FACP but the alarm signals did not report off site. Provide as-builts of changes prior to a final sign off.

Call prior to going Phone #: 6810381 >> Inspection requested via mobile web by Doug Lessa