INSP-Final Inspection | 7/17/2018 | 7/18/2018 | 7/18/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. New duct detector and installation arrangement accepted by plan review
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 6/20/2018 | 6/21/2018 | 6/21/2018 | A | CANC |
Troy Cobbley
|
|
|
The duct detector housing issue has not been resolved.
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 6/7/2018 | 6/8/2018 | 6/8/2018 | A | FAIL |
Troy Cobbley
|
|
|
We tested the duct smoke detector for shutdown and it functioned but the issue is per Potter tech support this duct detector, DDA, is not for outdoor use. A different detector listed for outdoor use, maybe with an enclosure, is going to need to be submitted/approved/installed and tested.
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|