Permit Information
Permit NumberFIR18-00059
StatusFinaled
Name PROTEX
Site Address 5246 W OVERLAND RD
Project NameStep Ahead T.I.
Customer Number 
ePlanReviewYes
Description
Add notification and air handler shutdown in new tenant space. This work is associated with building permit BLD17-03952.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/27/20188/28/20188/28/2018APASS
DetailsTroy Cobbley
Permit finaled

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection8/22/20188/23/20188/23/2018PFAIL
DetailsJim Page
Notification did not sync or operate correctly, some devices worked, others did not, troubleshoot fire alarm system for proper operation.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection8/16/20188/16/20188/16/2018PFAIL
DetailsTroy Cobbley
As-builts are needed to show the two strobes that need their candella adjusted higher and the manual pull station that has been deleted. Several strobes I could not see the candella setting due to height and no ladder. No actual testing performed. Will need to be re-scheduled after as-builts are approved.


Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten