Permit Number | FIR18-00079 |
Status | Finaled |
Name |
TREASURE VALLEY FIRE PROTECTION
|
Site Address |
1262 E EXCHANGE ST
|
Project Name | CHARLIES PRODUCE TI |
Customer Number | |
ePlanReview | Yes |
Description |
[Charlie's Produce]
The fire sprinkler scope of work consists of a space being converted to a freezer. The existing upright piping and sprinklers will remain. A new ceiling is being added at 16’. New dry pendent sprinklers will be supplied from the existing branch lines. The existing system is a 4”x 2½” x 1½” grid
Location on Plan - Top Left
Commodity - Fruit is corrugated containers
Classification - III
Storage Type (rack, solid pile, etc.) - Rack
Pallet Type (wood or plastic) - Wood
Aisle Width - 8’
Height of Storage - 16’
Ceiling Height - 17’-10”
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - K=8.0, RA6112
High Temperature Sprinklers Required - Yes
Applicable NFPA Section - T 16.2.1.3.2, (c), Curve E, 16.2.1.3.4.1
Hydraulic Design Criterion - .37/2000, 65%, .24/2000
Hose Stream Requirements - 500
[BLD17-04372]
Permit for the installation of new 16-foot-tall steel storage racking per the approved plans the occupancy evaluation was completed under BLD17-03958. Storage will be single and double row steel racking utilizing wood pallets. This building is fully fire sprinklered; separate fire protection permits will be required for any modifications to the existing fire protection systems. SJA
Alternative Materials and Methods:
• There are no AMM at this time.
|