INSP-Final Inspection | 6/29/2018 | 6/29/2018 | 6/29/2018 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
Coltin Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 5/30/2018 | 5/30/2018 | 5/30/2018 | P | PASS |
Troy Cobbley
|
|
|
The hydro test for the FDC passed.
Colton Cox is the contact for this FDC Hydro inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 5/23/2018 | 5/29/2018 | 5/30/2018 | P | CANC |
Troy Cobbley
|
|
|
Wrong building was scheduled.
Colton Cox is the contact for this rough-in on 6 units. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Final Inspection | 4/27/2018 | 4/30/2018 | 4/30/2018 | A | FAIL |
Troy Cobbley
|
|
|
Need to pass the hydro test on the FDC
Robert would like this inspection at 11AM, if possible. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 4/27/2018 | 4/30/2018 | 4/30/2018 | A | FAIL |
Troy Cobbley
|
|
|
Overhead hydro test for the first and second floor systems passed. The hydro test for the FDC failed due to visible leakage on exterior wall
|
INSP-Supply line flush | 4/5/2018 | 4/5/2018 | 4/5/2018 | P | PASS |
Troy Cobbley
|
|
|
Underground supply line flush passed
|
INSP-Sprinkler Rough-in | 2/26/2018 | 2/28/2018 | 2/28/2018 | A | PASS |
Troy Cobbley
|
|
|
Piping rough-in and tenting inspection passed. Piping can be covered.
|